User guide
DEHUMIDIFIER PUR LINE
PLC 100
1, 2 Construction and working principle.
3, Main technical
specifications.
4, 5 Electrical drawings.
6, 7 Installation and method of
operation.
8 Maintenance
9 Trouble shooting.
Thank you for your confidence in purchasing a Pur Line dehumidifier.
Please read this operation manual carefully prior to start the unit and
keep this guide in a safe place for future reference.
This dehumidifier must be grounded properly and reliably.
CONSTRUCTION AND WORKING PRINCIPLE
GENERAL
This dehumidifier is computer
controled. You only need to specify the required humidity level on the control
panel between 75% RH and 45% RH and the
dehumidifier will maintained this % of hygrometry of the air.
This dehumidifier is
particularly useful for large areas, industrial sites, warehouses, large
basements, archives, laboratories, swimming pools (within allowed distances)
etc…

FIG.1 Croquis du PLC 100
Structure.
Main structure
includes : compressor, evaporator, condenser, centrifugal fan,
electromagnetic valve, temperature sensor and electronic panel board etc…

Working principle
This dehumidification process
is simply done by condensation of the moisture loaded in the air on a large set
of cold plates (evaporator) with a compressor and a refrigeration system.
The water resulting from this
condensation process is evacuated through a drain.
Defrost.
When
the ambient temperature is between 5°C to 15°C and the dehumidifier is in
function, the evaporator will be covered with frost. A sensors informs the
electronic board and the defrosting process then starts automatically. When the
defrost is completed, the dehumidification process resume itself. The unit will
work in relatively low ambient temperatures.
Model PLC
100
|
Dehumidifier capacity
at 60% R.H. 3.2 Kg /
h |
|
at 70% R.H. 4.2 Kg / h |
Voltage V 220
±10%
Frequency Hz 50
Rated
current A
8,0
Rated
input power KW 1,7
Maximum
input power KW 2,1
Suction pressure Ma 0,55
Discharge pressure Ma 1,8
Air
flow m3/h 900
Noise pressure dB
(A) 58
Refrigerant / charge kg
R407C 1,2
Dimensions ( D x L x H ) mm 439 x
540 x 1023
Weight kg 64
Main switch / Fuse A 15
/ 15
Attention :
Nominal working conditions 27.0°C (DB), 21.2°C (WB)
Maximum working conditions 32.0°C
(DB), 23,0°C (WB)
Minimum working temperature
conditions 5.0°C (DB), 2,1°C (WB)
|
Notice In order to preserve your warranty privileges,
please use this unit under the prescribed environment and temperature
conditions. The life span of the unit will be shorten in the
unit is used in conditions exceeding these we recommend. |
Electrical diagram principle

|
C1 : Fan capacitor AP : Main control board M2 : Compressor T : Transformer FU1: Fuse box FU2: Fuse box |
M1 : Fan motor C2 : Compressor capacitor YV : Electromagnetic
defrost valve K : Miniature large power relay ST : Humidity sensor
RT : Defrost temperature sensor
|
|
Attention: This diagram is for reference only. Please review diagram on unit in
case of maintenance. |

B. blue BL. black BR. brown G. green GR. grey O.
orange
R . red W. white Y. yellow
FIG4. PLC100 Electrical diagram
Location :
Electrical supply
Installation :
Attention :
This unit is not suitable for marine and kitchen sites. The life span of
the unit may be shorten if the function is allowed in a caustic or polluted gas
environment
OPERATING METHOD.
:

Fig.5 PLC100 Control panel
When the supply cord is
connected to the power main, the « Power » light (red) comes on. The
unit is on mode “Stand-by”
« MANUAL » operation
Press « MANUAL » switch, the delay light (red) is on. After 3
minutes, the run light (green) is on, the compressor and the fan starts
working, the unit is in dehumidification mode.
Press « MANUAL »
switch again, the run light is off, the unit stops working, the unit is in
standby mode.
« Automatic » operation.
Press
« AUTO » switch, the upper and lower limit lights (green) of the
humidity are on, and the humidity control indicates the scope of the humidity.
The unit is in the auto run mode.
Humidity selection level.
If you select the
« AUTO » switch position, the upper and lower limit lights (green)
come on and the humidity control indicates the preset humidity range required.
Select “UP” or “LOWER” to obtain the required relative humidity rate. At this
time, the computer control system will evaluate the ambient humidity and
command the unit to start dehumidify if necessary. If ambient humidity is less
than required, the system will automatically stop.
Compressor protection.
The
« DELAY » light is designed to temporary postpone the compressor
start in case of sudden start / stop actions. The starting delay time is of 3
minutes. After 3 minutes of waiting time, the compressor will resume operation.
Automatic defrost
The orange light
« DEFROST » will come on when the system is defrosting itself
Attention.
-
The
electronic switches on the control panel are of the “key touch” type. Please do
not knock hard on these.
-
The
humidity sensor is fragile. Please clean it carefully periodically if dusty to
ensure more precision. Please correct or replace if defective.
-
When the
unit is not in use, please disconnect from the power main.
MAINTENANCE
Switch
off the power source before maintenance.
Due to the accumulation of
dust, the air filter must be cleaned regularly. (at least one a month). If
necessary (according to local conditions) this could be done every week or even
daily.
Removal of Front grille
Remove the 2 screws from the
upper part of the panel, press the panel downward and pull forward. See Fig.6

Romove the air filter
Draw the iar filter towards
the top. See Fig.6.
Clean the air filter
Gently tap the air filter to
remove the dust; user a vacuum cleaner or place the filter in warm water (less
than 40°C); wash and brush it and rinse.
Attention :
-
The air
filter should not be exposed directly to sun or fire to avoid distortions.
-
The
air-filter must be in position prior to starting the dehumidifier.
|
ATTENTION : We recommend you have your
unit maintained periodically by a professional to insure a regular life span. |
Trouble shooting
The unit does not work Power failure Check power source
Not plugged in Plug in
Fuse Replace
fuse
Does not dehumidify No moisture in the air Shut down
Air filter is blocked
off Clean filter
Door or window open Close all openings
Water leakage Unit is tilted Install
unit on flat surface
Drain pipe is blocked Remove
front panel and wipe off the dirt
“Power protection” light The temperature sensor is open Replace the T° sensor
or short circuit
Unit does not defrost The T° sensor is loose Reinstall T° sensor
Gas valve is defective Replace gas valve
If unit still does not
function, please contact your dealer or repair depot.
When the dehumidifier starts and stops, there is a normal noise due to
the refrigerant cycling. It is also normal to feel warm air coming from the
exhaust side.
|
NOTICE. Please disconnect unit when not in use. The dehumidifier must be grounded properly. If the supply cord is damaged, it must be replaced
by the installer or a qualified party. Please keep this user guide for future reference. |
Warranty : 1 year to
first buyer.
To insure of rights to
warranty privileges, please insure to include with claim your proof of purchase
showing purchase date.
WinEurope SA – France
Email : info@purline.com
Internet : www.purline.com